Electricity meters, smart metering solutions
en
Elgama-Elektronika Ltd
info@elgama.eu
+370 5 2375 000
Back to the list

EPQS

EPQS

Ask about item

Product inquiry form

*

* Marked fields are required

The EPQS meter is a multifunction device for measurement of electric energy in four-quadrants and is approved in accordance with IEC 62053-11, IEC 62053-22, IEC 62053-21, IEC 62053-23. Meter operates in 3- or 4-wire networks and can be direct connection (accuracy class 1) or CT or CT/VT connection (accuracy class 0.2s or 0.5s). EPQS meter can be easily incorporated into AMR systems. It has power quality monitoring capabilities and is designed to meet the most ultimate demands from utilities and other clients.

  • Measurement of active, reactive energy and maximum demand
  • Accuracy class: for active energy - 0.2s or 0.5s (connection via transformers), 1.0s (direct connection), for reactive energy - 2.0s
  • Up to 8 energy tariffs
  • Optical and electrical communication interfaces
  • Up to 8 programmable electrical pulse outputs (S0)
  • Load profiles and instantaneous values
  • Power quality monitoring
  • Internal clock with events logbook (power outages, reverse phase sequence, magnetic field influence, main cover or terminal cover openings, meter programming)
  • Security features (hardware protection, software protection)
System Three-phase 4-wire or 3-wire
Accuracy class:
- for active energy
- for reactive energy

0.2s, 0.5s (CT connection), 1.0 (direct connection)
2.0
Reference voltage, Un:
- 4 wire networks
- Multi range
- 3 wire networks

3x57,7/100; 3x63,5/110; 3x69,2/120; 3x120/208; 3x127/220; 3x220/380
3x230/400
3x57,7 ...230/100 ...400; 3x100; 3x110; 3x220; 3x230; 3x120
Reference (maximum) current, Ib (Imax)
- Direct connection, A
- CT or CT/VT connection, A

10(100)
5(6); 5(10); 1(2); 1(6)
Current threshold 0,1% Ib (if direct connection - 0,4% In)
Reference Frequency, Hz 50 or 60
Meter constant, imp/kWh (imp/kVArh) <130000
Power consumption:
- In voltage circuit
- In current circuit

< 0,9 W; < 2,5 VA
< 0,3 VA (< 0,05 CT or CT/VT connection)
Temperature ranges:
- Meter operating
- Meter storage

-40°C to +60°C
-50°C to +70°C
Accuracy of internal real-time clock < 0,5 s/24 h (T = 23 °C)
Backup power supply Li-ion battery or Super Cap (rechargeable)
Operation duration using only backupį:
- Li-ion battery
- Super Cap

> 16 years
> 7 days
Case UV stabilized polycarbonate
Insulation II Protection class
Protection class IP51
Dimensions, mm 325 x 177 x 55