New generation three-phase electricity meter designed for industrial metering. With accuraccy class 0.2s, GAMA 300 measures active and reactive energy and may be single-tariff or multi-tariff.


  • Measurement of active energy (bidirectional), reactive energy (in 4-quadrants) and maximum demand
  • Accuracy class 0.2s (IEC 62053-22)
  • Single or Multi-tariff (up to 6 tariffs)
  • Optical and electrical communication interfaces in accordance with IEC 62056-21 and/or DLMS/COSEM
  • Internal communication modules (USB host, RS485, Ethernet), powering of external modem
  • Internal real time clock
  • Load and billing profiles, instantaneous values
  • The second independent load profile
  • Load profile with phase energy and power values
  • Extended anti-tamper features
  • High-level security (encryption and authentication)
  • Event logbook (power outage, power over-limit, reverse current flow, influence of magnetic field, opening of meter cover, opening of terminal cover, clock setting, parameter change, internal error, firmware update)
  • Power quality monitoring (over-voltage, under-voltage, over-current)
  • Registration of line and transformer losses on the basis of I2h and U2h measurements

Connection type

Three-phase 4-wire

Accuracy class:

-for active energy

-for reactive energy

 

0.2s (IEC 62053-22)

0.5s (IEC 62053-22 by substituting cos(φ) to sin(φ))

Reference voltage, V:

-4-wire network

-multi-range

3x220/380; 3x230/400; 3x240/415; 3x57,7/100; 3x63,5/110; 3x69,2/120; 3x120/208; 3x127/220

3x57,7/100…230/400

Reference In (maximum) current, A:

1(1,25); 1(6); 5(6,25); 5(10)

Starting current

0,1% In

Reference frequency, Hz

50 or 60

Meter constant, imp/kWh, imp/kVArh

1...60000

Power consumption per phase:

-in voltage circuit

-in current circuit

<1.0 VA (< 0,5 W)

<0,5 VA

Temperature range

-40°C to +70°C

Accuracy of internal real-time clock

< 0,5 s/24 h (T = 23 °C)

Backup power supply of clock

Li-ion battery and/or Super Cap

Li-ion battery

changeable or internal

Operation duration using only backup:
-Li-ion battery
-Super Cap


> 12 years
up to 7 days

Case

UV stabilized polycarbonate

Insulation

Protective class II

Protection class

IP53 (optional IP54)

Dimmensions, mm

260 x 175 x 80

Weight, kg

< 1,5