Indicator status |
Meaning |
|
|
|
L1, L2, L3 |
|
|
Off |
Off |
No network voltage |
|
On |
Off |
No load current |
|
Blinking |
On |
Fault of the meter |
|
Off |
On |
Normal operation of the meter |
|
Off |
Some blinking |
Reverse current flow in |
|
Off |
In series on-off |
Reverse voltage phase sequence |
|
Off |
Some off |
No voltage or current |
|
Ratings |
|
| System | Three-phase 4-wire or 3-wire |
| Accuracy class | Class 1.0 or Class 2.0 |
| Reference voltage, Un: 4 wire networks 3 wire networks |
3x57,7/100; 3x63,5/110; 3x69,2/120; 3x120/208; 3x127/220; 3x220/380; 3x230/400 3x100; 3x110; 3x220; 3x230; 3x120 |
| Reference (max.) current, Ib (Imax): Direct connection, A CT or CT/VT connection, A |
5(60); 5(80); 10(60); 10(100); 5(100) 1(1,2); 5(6); 5(10) |
| Current threshold | 0,4% Ib (0,2% In if CT or CT/VT connection) |
| Reference Frequency, Hz | 50 or 60 |
| Meter constant, imp/kWh | 500 (direct connection) 5000 (CT or CT/VT connection) |
| Power consumption: In voltage circuit In current circuit |
< 0,5 W; < 2 VA < 0,3 VA |
| Temperature ranges: Meter operating Meter storage |
-40°C to +60°C -50°C to +70°C |
|
Case & Dimensions |
|
| Case | UV stabilized polycarbonate |
| Insulation | Protective class II |
| Degree of protection | IP51 |
| Dimensions, mm | 325 x 177 x 55 |
| Weight, kg | < 1,5 |