Single-phase static electricity meter GAMA 100 is developed for residential applications and is approved according to EN 50470-1, EN 50470-3, IEC 62052-11 and IEC 62053-21. The electricity meter satisfies the requirements of Directive 2004/22/EC of the European Parliament and of the Council of 31 March 2004 on measuring instruments 
GAMA 100 can be simple, single-tariff or sophisticated multi-tariff meter with extended functionality. Meter can be provided with various optional features - including maximum demand measurement, possibility to connect meter to AMR system, extended anti-tamper capability, relay output, changeable (without uninstalling meter from site) Li-ion battery.

Features: 

Measuring

Meter operates in single-phase electricity networks and independently from current flow direction measure:
  • Active energy with accuracy class 1.0 (B) or 2.0 (A);
  • Instantaneous power;
  • [Optional] Maximum Demand with programmable integration periods 15, 30, 60 min;
  • [Optional] Measurement in two channels (in phase and neutral lines).
  • [Optional] Instantaneous values (A, V) - readout only from communication interfaces;

Tariff module

Multifunctional GAMA 100 meter has internal real-time clock with Li-ion battery ([Optional] can be changeable without uninstalling meters from site) or Super-cap backup and complex tariff structure (Time-Of-Use):
  • Number of energy tariffs
  • Up to 4 tariffs;
  • Number of seasons
  • Up to 12 tariff seasons;
  • Number of week profiles
  • Up to 10-week profiles;
  • Number of day profiles
  • Up to 15-day profiles;
  • Special days
  • Up to 365 days;
  • [Optional] Number of
        maximum demand tariffs
  • Up to 4 tariffs.

    Data storage

    GAMA 100 meter has non-volatile memory, which allows to store metering data without influence of power outages. Capacity of stored data:
  • Total energy  
  • from installation date;
  • Monthly energy
  • last 16 months;
  • Events logbook records
  • up to 10 records of each event type;
  • [Optional] Monthly maximum demand
  • last 16 months.

    Billing

    At the end of the billing period, the billing period reset signal triggers the storage of the current values to the non-volatile memory. The billing period reset may be initiated:
  • Manually
  • by pressing push button;
  • Automatically (programmable)
  • on decade days;
    on ½ month;
    on predefined day.

    Communications

    Meter has optical communication interface in accordance with IEC 62056-21. Optical communication interface allows the user to read data and program meter in the field or in the workshop.
    [Optional] GAMA 100 meter can have electrical communication interface (20 mA current loop or RS485) with protocol in accordance with IEC 62056-21 or IEC 62056-31, allowing connection of meters to AMR system through external GSM/GPRS, RF, PSTN, and LAN controllers.

    Outputs

  • Electric pulse output (S0)
  • LED test output for active energy
  • [Optional] Relay, normally open contacts are connected:
    • When specified energy tariff is valid;
    • For two programmed periods during the 24-hour interval (periods are set in 15 minutes step).
  • Security features

    Hardware protection allows only authorized persons to access meter:
  • Two seals on main cover;
  • One seal on terminal cover;
  • [Optional] optical communication interface sealing;
  • [Optional] current measurement in neutral.
  • Software protection allows only authorized persons to program meter with software for meter programming and data reading:
  • Meters programming is protected by password; if incorrect password is entered four times in a day, the communication interfaces will be locked for 24 hours. During that period communication is impossible.
  • Meter with internal clock has Events logbook, registering the following events:
  • Power outages  
  • last 10 events with date & time;
  • Meter programming
  • last 10 events with date & time;
  • Magnetic field influence
  • last event with date & time;
  • [Optional] main cover openings
  • last event with date & time;
  • [Optional] terminal cover openings
  • last event with date & time.

    Display

    GAMA 100 meter is equipped with LCD (Liquid crystal display). LCD contains 8 digits with programmable decimal point: 8-5 for whole numbers and 0-3 digits for decimal numbers. LCD displays majority of data accumulated in meter and parameterization constants. Features:
  • Cyclic (automatic) and static (manual) data scroll;
  • Data indication on LCD during power outages;
  • Reverse current flow indication;
  • Li-ion battery (Super-cap) status indication;
  • Menu control by pushbutton or [optional] light signals.

  • Technical Specification:

    Ratings

     
    System Single-Phase 2-wire
    Accuracy class class 1.0 or 2.0 (IEC 62053-21);
    class B or A (EN 50470-3)
    Reference voltage, Un 100V; 120V; 127V; 220V; 230V;
    special on request
    Reference (maximum) current, Ib (Imax) 5(60) A; 5(80) A; 5(100)A;
    10(60) A; 10(80)A; 10(100) A
    Current threshold 0,4% Ib
    Reference Frequency, Hz 50 or 60
    Meter constant, imp/kWh 1...19999, programmable
    Power consumption:
    In voltage circuit
    In current circuit

    < 0,75W; < 1 VA
    < 0,05 VA
    Temperature ranges:
    Meter operating
    Meter storage

    -40°C to +70°C
    -40°C to +70°C

    Internal real-time clock

     
    Accuracy < 0,5 s/24 h (T = 23 °C)
    Backup power supply Li-ion battery or Super Cap (rechargeable)
    Operation duration using only backup:
    Li-ion battery
    Super Cap

    > 16 years
    > 7 days

    Case & Dimensions

     
    Case UV stabilized polycarbonate
    Insulation Protective class II
    Protection class IP53 
    Dimensions, mm 180 x 130 x 65
    Weight, kg 0,6

    Downloads: