GAMA 100
Single-phase static electricity meter GAMA 100 is developed for residential applications and is approved according to EN 50470-1, EN 50470-3, IEC 62052-11 and IEC 62053-21. The electricity meter satisfies the requirements of Directive 2004/22/EC of the European Parliament and of the Council of 31 March 2004 on measuring instruments
GAMA 100 can be simple, single-tariff or sophisticated multi-tariff meter with extended functionality. Meter can be provided with various optional features - including maximum demand measurement, possibility to connect meter to AMR system, extended anti-tamper capability, relay output, changeable (without uninstalling meter from site) Li-ion battery.
Features:
Measuring
Meter operates in single-phase electricity networks and independently from current flow direction measure:
- Active energy with accuracy class 1.0 (B) or 2.0 (A);
- Instantaneous power;
- [Optional] Maximum Demand with programmable integration periods 15, 30, 60 min;
- [Optional] Measurement in two channels (in phase and neutral lines).
- [Optional] Instantaneous values (A, V) - readout only from communication interfaces;
Tariff module
Multifunctional GAMA 100 meter has internal real-time clock with Li-ion battery ([Optional] can be changeable without uninstalling meters from site) or Super-cap backup and complex tariff structure (Time-Of-Use):
|
Number of energy tariffs |
Up to 4 tariffs; |
|
Number of seasons |
Up to 12 tariff seasons; |
|
Number of week profiles |
Up to 10-week profiles; |
|
Number of day profiles |
Up to 15-day profiles; |
|
Special days |
Up to 365 days; |
[Optional] Number of
maximum demand tariffs |
Up to 4 tariffs. |
Data storage
GAMA 100 meter has non-volatile memory, which allows to store metering data without influence of power outages. Capacity of stored data:
|
Total energy |
from installation date; |
|
Monthly energy |
last 16 months; |
|
Events logbook records |
up to 10 records of each event type; |
|
[Optional] Monthly maximum demand |
last 16 months. |
Billing
At the end of the billing period, the billing period reset signal triggers the storage of the current values to the non-volatile memory. The billing period reset may be initiated:
|
Manually |
by pressing push button; |
|
Automatically (programmable) |
on decade days;
on ½ month;
on predefined day. |
Communications
Meter has optical communication interface in accordance with IEC 62056-21. Optical communication interface allows the user to read data and program meter in the field or in the workshop.
[Optional] GAMA 100 meter can have electrical communication interface (20 mA current loop or RS485) with protocol in accordance with IEC 62056-21 or IEC 62056-31, allowing connection of meters to AMR system through external GSM/GPRS, RF, PSTN, and LAN controllers.
Outputs
Electric pulse output (S0)
LED test output for active energy
[Optional] Relay, normally open contacts are connected:
- When specified energy tariff is valid;
- For two programmed periods during the 24-hour interval (periods are set in 15 minutes step).
Security features
Hardware protection allows only authorized persons to access meter:
Two seals on main cover;
One seal on terminal cover;
[Optional] optical communication interface sealing;
[Optional] current measurement in neutral.
Software protection allows only authorized persons to program meter with software for meter programming and data reading:
Meters programming is protected by password; if incorrect password is entered four times in a day, the communication interfaces will be locked for 24 hours. During that period communication is impossible.
Meter with internal clock has Events logbook, registering the following events:
|
Power outages |
last 10 events with date & time; |
|
Meter programming |
last 10 events with date & time; |
|
Magnetic field influence |
last event with date & time; |
|
[Optional] main cover openings |
last event with date & time; |
|
[Optional] terminal cover openings |
last event with date & time. |
Display
GAMA 100 meter is equipped with LCD (Liquid crystal display). LCD contains 8 digits with programmable decimal point: 8-5 for whole numbers and 0-3 digits for decimal numbers. LCD displays majority of data accumulated in meter and parameterization constants. Features:
Cyclic (automatic) and static (manual) data scroll;
Data indication on LCD during power outages;
Reverse current flow indication;
Li-ion battery (Super-cap) status indication;
Menu control by pushbutton or [optional] light signals.
Technical Specification:
|
Ratings
|
|
| System |
Single-Phase 2-wire |
| Accuracy class |
class 1.0 or 2.0 (IEC 62053-21);
class B or A (EN 50470-3) |
| Reference voltage, Un |
100V; 120V; 127V; 220V; 230V;
special on request |
| Reference (maximum) current, Ib (Imax) |
5(60) A; 5(80) A; 5(100)A;
10(60) A; 10(80)A; 10(100) A |
| Current threshold |
0,4% Ib |
| Reference Frequency, Hz |
50 or 60 |
| Meter constant, imp/kWh |
1...19999, programmable |
Power consumption:
In voltage circuit
In current circuit |
< 0,75W; < 1 VA
< 0,05 VA |
Temperature ranges:
Meter operating
Meter storage |
-40°C to +70°C
-40°C to +70°C |
|
Internal real-time clock
|
|
| Accuracy |
< 0,5 s/24 h (T = 23 °C) |
| Backup power supply |
Li-ion battery or Super Cap (rechargeable) |
Operation duration using only backup:
Li-ion battery
Super Cap |
> 16 years
> 7 days |
|
Case & Dimensions
|
|
| Case |
UV stabilized polycarbonate |
| Insulation |
Protective class II |
| Protection class |
IP53 |
| Dimensions, mm |
180 x 130 x 65 |
| Weight, kg |
0,6 |
Downloads:
Product brochure
More information about the meter available to download can be found
here
Other products >>