|LT |EN |RU |SP|
  HOMEMAILSITEMAPPRINT
Portable meter testing device

PTD-3G

PTD - 3G (Portable Testing Device) is a portable electronic device for on site meter testing, measurement of instantaneous values and profile recording. The device also provides some features of network quality monitoring. It is suitable for testing of single-phase and three-phase electricity meters on site, for energy quality and network parameters monitoring.
Wide range of functions, user - friendly interface, and sizeable graphical LCD applicable for diagram indication make the working with this device easy, accurate and attractive.

Application

  • On site testing of inductive and electronic single-phase and three-phase electricity meters
  • Power quality monitoring (according to the standard IEC50160)
  • Measurement of instantaneous values
  • Profile recording


  • Functions
  • Active, reactive and apparent energy measurement with error calculation (percentage):
    • Measurement error of active energy (cosφ=1):
      • ±0,5 % with clamps A (0,5...100 A);
      • ±0,5 % with clamps B (1...1000 A);
      • ±0,5 % with clamps C (10...1500 A).
  • Active, reactive and apparent energy measurement with start / stop function
  • Meter accuracy, constant, wiring, no load/start condition testing
  • Active, reactive, apparent power measurement (per phase and aggregate):
    • Measurement error:
      • ±0,5 % with clamps A (0,5...100 A)
      • ±0,5 % with clamps B (1...1000 A)
      • ±0,5 % with clamps C (10...1500 A)
  • Voltage measurement:
    • Frequency range: 45...65 Hz;
    • Error: ±0,2 % in range 50 ...265 V
  • Current measurement:
    • Frequency range: 45...65 Hz;
    • Current range: depends on current clamps;
    • Measurement error: 
      • ±0,5 % with clamps A (0,5...100 A)
      • ±0,2 % with clamps B (1...1000 A)
      • ±0,5 % with clamps C (10...1500 A)
  • Power factor measurement (per phase and aggregate):
    • Measurement range -1...+1;
    • Resolution: 0,01
  • Frequency measurement:
    • Range 45...65 Hz;
    • Resolution 0,01 Hz
  • Harmonics analysis:
    • Harmonic components from 2 to 30 in - percent of the fundamental wave;
    • Numeric values of each harmonic component;
    • Chart in a logarithmic scale
  • Vector diagram displaying
  • Measurement of angles:
    • Voltage phase shift angles (per phase and aggregate), resolution: 0,1°
    • Angles between voltage phases, resolution: 1°
  • Power quality measurement:
    • Voltage variation measurement (according EN50160)
    • Frequency variation measurement (according EN50160)
    • Total harmonics distortion
    • Power outages

    Data Storage
  • Up to 64 records of on site meter testing results. Each record can include up to 4 test results (if all tests were performed by one request)
  • Up to 32 records of energy quality monitoring. Each record includes information about voltage, frequency variations
  • Up to 64 snapshots of instantaneous values (including vector diagram and harmonics)
  • Recording of up to 6 profiles for chosen measuring values with measurement period from 10 s to 60 min.


  • Features
  • Powered by measuring circuits
  • Wide current measuring range (500mA ... 1500A)
  • Sizeable graphical LCD indicator (128x128 dots) with backlight
  • Electronic test output
  • RS 232 or USB interface for connection to PC
  • Current loop interface according to IEC62056-31 for connection to AMR system

  • Technical Specification:

    Power supply

     
    Powered by voltage measuring circuits 45 V... 276 V, consumption: < 2 W per phase
    Powered by auxiliary circuit 45 V... 276 V, consumption: < 6 W
    Profiles  
    Number of channels for profile recording: 6 with 25 different parameters available
    One of 5 registration algorithms for
    each channel:
    Minimum value per measurement period
    Maximum value per measurement period
    Average value per measurement period
    Snapshot at the end of measurement period
    Standard deviation per measurement period
    Range of measurement period: 10s...60 min
    Current clamps  
    Current range 0,5 A...100 A (Clamps A)  
    Electrical safety:   
      Insulation:   
      Pollution:   
      Safety class:   
      Operating voltage:      
        Bare conductor      
        Isolated conductor

    Dual
    Level 2
    Class III

    30V
    600V
    Overload: 170 A
    Protection level: IP40
    Weight: ~ 0,16 kg
    Max. Clamping capacity:
      Cable, mm:
      Bus bar, mm:

    Ø12
    17 x 15
    Current range 1 A...1000 A (Clamps B)  
    Electrical safety:
      Insulation: 
      Pollution:
      Safety class:
      Operating voltage:

    Dual
    Level 2
    Class III
    600V
    Overload: 1200 A
    Protection level: IP40
    Weight: ~ 0,55 kg
    Max. Clamping capacity:
      Cable, mm:
      Bus bar, mm:

    Ø52
    50 x 5
    Current range 10 A...1500 A (Clamps C)  
    Electrical safety:
      Insulation:
      Pollution:
      Safety class: 
      Operating voltage:
        Bare conductor
        Isolated conductor

    Dual
    Level 2
    Class III

    600V,
    1000V
    Overload: 1800 A
    Protection level: IP20
    Scanning head  
    Usable with: Induction and electronic meters
    Supply voltage: 6...12 V
    Dimensions: 270mm x 95mm x 80mm
    Electronic block  
    Max. Clamping capacity:
      Cable, mm:
      Bus bar, mm:

    Ø80
    100x 55 or 120 x 45
    Housing: Hard plastic
    Dimension: 157 x 189 x 67 mm
    Weight: 0.8 kg
    Operation temperature: -20 °C ... + 50 °C
    Protection level: IP 40

    Downloads:
     
     Product brochure

    More information about the device available to download could be found here