PTD-3G
PTD - 3G (Portable Testing Device) is a portable electronic device for on site meter testing, measurement of instantaneous values and profile recording. The device also provides some features of network quality monitoring. It is suitable for testing of single-phase and three-phase electricity meters on site, for energy quality and network parameters monitoring.
Wide range of functions, user - friendly interface, and sizeable graphical LCD applicable for diagram indication make the working with this device easy, accurate and attractive.
Application
On site testing of inductive and electronic single-phase and three-phase electricity meters
Power quality monitoring (according to the standard IEC50160)
Measurement of instantaneous values
Profile recording
Functions
Active, reactive and apparent energy measurement with error calculation (percentage):
- Measurement error of active energy (cosφ=1):
- ±0,5 % with clamps A (0,5...100 A);
- ±0,5 % with clamps B (1...1000 A);
- ±0,5 % with clamps C (10...1500 A).
Active, reactive and apparent energy measurement with start / stop function
Meter accuracy, constant, wiring, no load/start condition testing
Active, reactive, apparent power measurement (per phase and aggregate):
- Measurement error:
- ±0,5 % with clamps A (0,5...100 A)
- ±0,5 % with clamps B (1...1000 A)
- ±0,5 % with clamps C (10...1500 A)
Voltage measurement:
- Frequency range: 45...65 Hz;
- Error: ±0,2 % in range 50 ...265 V
Current measurement:
- Frequency range: 45...65 Hz;
- Current range: depends on current clamps;
- Measurement error:
- ±0,5 % with clamps A (0,5...100 A)
- ±0,2 % with clamps B (1...1000 A)
- ±0,5 % with clamps C (10...1500 A)
Power factor measurement (per phase and aggregate):
- Measurement range -1...+1;
- Resolution: 0,01
Frequency measurement:
- Range 45...65 Hz;
- Resolution 0,01 Hz
Harmonics analysis:
- Harmonic components from 2 to 30 in - percent of the fundamental wave;
- Numeric values of each harmonic component;
- Chart in a logarithmic scale
Vector diagram displaying
Measurement of angles:
- Voltage phase shift angles (per phase and aggregate), resolution: 0,1°
- Angles between voltage phases, resolution: 1°
Power quality measurement:
- Voltage variation measurement (according EN50160)
- Frequency variation measurement (according EN50160)
- Total harmonics distortion
- Power outages
Data Storage
Up to 64 records of on site meter testing results. Each record can include up to 4 test results (if all tests were performed by one request)
Up to 32 records of energy quality monitoring. Each record includes information about voltage, frequency variations
Up to 64 snapshots of instantaneous values (including vector diagram and harmonics)
Recording of up to 6 profiles for chosen measuring values with measurement period from 10 s to 60 min.
Features
Powered by measuring circuits
Wide current measuring range (500mA ... 1500A)
Sizeable graphical LCD indicator (128x128 dots) with backlight
Electronic test output
RS 232 or USB interface for connection to PC
Current loop interface according to IEC62056-31 for connection to AMR system
Technical Specification:
|
Power supply
|
|
| Powered by voltage measuring circuits |
45 V... 276 V, consumption: < 2 W per phase |
| Powered by auxiliary circuit |
45 V... 276 V, consumption: < 6 W |
| Profiles |
|
| Number of channels for profile recording: |
6 with 25 different parameters available |
One of 5 registration algorithms for
each channel: |
Minimum value per measurement period
Maximum value per measurement period
Average value per measurement period
Snapshot at the end of measurement period
Standard deviation per measurement period |
| Range of measurement period: |
10s...60 min |
| Current clamps |
|
| Current range 0,5 A...100 A (Clamps A) |
|
Electrical safety:
Insulation:
Pollution:
Safety class:
Operating voltage:
Bare conductor
Isolated conductor |
Dual
Level 2
Class III
30V
600V |
| Overload: |
170 A |
| Protection level: |
IP40 |
| Weight: |
~ 0,16 kg |
Max. Clamping capacity:
Cable, mm:
Bus bar, mm: |
Ø12
17 x 15 |
| Current range 1 A...1000 A (Clamps B) |
|
Electrical safety:
Insulation:
Pollution:
Safety class:
Operating voltage: |
Dual
Level 2
Class III
600V |
| Overload: |
1200 A |
| Protection level: |
IP40 |
| Weight: |
~ 0,55 kg |
Max. Clamping capacity:
Cable, mm:
Bus bar, mm: |
Ø52
50 x 5 |
| Current range 10 A...1500 A (Clamps C) |
|
Electrical safety:
Insulation:
Pollution:
Safety class:
Operating voltage:
Bare conductor
Isolated conductor |
Dual
Level 2
Class III
600V,
1000V |
| Overload: |
1800 A |
| Protection level: |
IP20 |
| Scanning head |
|
| Usable with: |
Induction and electronic meters |
| Supply voltage: |
6...12 V |
| Dimensions: |
270mm x 95mm x 80mm |
| Electronic block |
|
Max. Clamping capacity:
Cable, mm:
Bus bar, mm: |
Ø80
100x 55 or 120 x 45 |
| Housing: |
Hard plastic |
| Dimension: |
157 x 189 x 67 mm |
| Weight: |
0.8 kg |
| Operation temperature: |
-20 °C ... + 50 °C |
| Protection level: |
IP 40 |