Portable power analyser
PTD-2G
PTD-2G is a portable power analyzer for measurement and registration of alternating low voltage electricity energy network parameters. The device could be connected directly to voltage lines and to current lines through current clamps or directly. The device could be used in assistance to electricity thief detection. PTD-2G has communication interface for remote data transmission.

Application
On site testing of electricity network parameters;
Assistance to electricity thief detection;
Power quality monitoring;
Measurement of instantaneous values;
Measured data profile recording.
Functions
Active, reactive and apparent energy measurement in up to 8 tariffs;
Maximum demand measurement in up to 8 tariffs;
Active, reactive, apparent power measurement:
Voltage measurement:
Current measurement:
Power factor measurement:
Frequency measurement:
Power quality measurement:
Load profile recording:
Data Storage
PTD-2G device has 1 MB of non-volatile memory, which allows to store metering data without influence of power outages. Capacity of stored data:

Application
Functions
- Measurement error:
- 0,5 % with clamps MG8;
- 0,5 % direct
- Error: ±0,5 % in range 50 ...254 V
- Current range: depends on current clamps;
- Measurement error:
- ±0,5 % with clamps MG8;
- ±0,5 % direct
- Measurement range -1...+1;
- Resolution: 0,01;
- Range 45...65 Hz;
- Resolution 0,01 Hz;
- Voltage variation measurement;
- Frequency variation measurement;
- Power outages;
- Number of channels: 8 (+A, -A, R1, R2, R3, R4, +W, -W);
- Load profile capacity: up to 341 days with integration period of 60 minutes;
- Programmable integration period: from 30 sec to 60 min.
Data Storage
PTD-2G device has 1 MB of non-volatile memory, which allows to store metering data without influence of power outages. Capacity of stored data:
|
|
[T1...T8, TS]; |
|
|
[T1...T8, TS], at least 54 months; |
|
|
[T1...T8, TS], at least 100 days; |
|
|
[T1...T8]; |
|
|
[T1...T8], at least 54 months, with date and time; |
|
|
[T1...T8], at least 100 days, with date and time; |
|
|
up to 8 channels; |
|
|
up to 16 programmable channels for any of 26 instantaneous value; |
Features
Technical specification:
| Ratings | |
| Rated voltage, V: | 50 ... 276V |
| Measuring period, s | 1 |
| Power consumption, VA: | 2/phase |
| Frequency range, Hz: | 45 ... 65 |
| Operating temperatures | -10°C … +50°C |
| Storage and transportation temperatures | -35°C … +50°C |
| Relative humidity: | Up to 80% (t=25°С) |
| Current clamps | |
| Current range 0,1 A...200 A (Clamps MG8) | |
| Phase voltage, V | 50…254 |
| Line-to-line voltage, V | 100…440 |
| Current range 0,001 A...0,3 A (direct connection) | |
| Phase voltage, V | 50…254 |
| Line-to-line voltage, V | 100…440 |
| External backup power supply | |
| Input/output voltage, V | »230/(=12..14) |
| Current, mA | 500 |
| Case & Dimensions | |
| Case: | UV stabilized polycarbonate |
| Insulation: | Protective class 2 |
| Measuring unit dimensions: | 157 x 189 x 67 mm |
| Measuring unit weight: | 2 kg |
| Protection level: | IP 52 |