|LT |EN |RU |SP|
  HOMEMAILSITEMAPPRINT
Portable power analyser

PTD-2G

PTD-2G is a portable power analyzer for measurement and registration of alternating low voltage electricity energy network parameters. The device could be connected directly to voltage lines and to current lines through current clamps or directly. The device could be used in assistance to electricity thief detection. PTD-2G has communication interface for remote data transmission.

Application
  • On site testing of electricity network parameters;
  • Assistance to electricity thief detection;
  • Power quality monitoring;
  • Measurement of instantaneous values;
  • Measured data profile recording.


  • Functions
  • Active, reactive and apparent energy measurement in up to 8 tariffs;
  • Maximum demand measurement in up to 8 tariffs;
  • Active, reactive, apparent power measurement:
    • Measurement error:
      • 0,5 % with clamps MG8;
      • 0,5 % direct
  • Voltage measurement:
    • Error: ±0,5 % in range 50 ...254 V
  • Current measurement:
    • Current range: depends on current clamps;
    • Measurement error:
      • ±0,5 % with clamps MG8;
      • ±0,5 % direct
  • Power factor measurement:
    • Measurement range -1...+1;
    • Resolution: 0,01;
  • Frequency measurement:
    • Range 45...65 Hz;
    • Resolution 0,01 Hz;
  • Power quality measurement:
    • Voltage variation measurement;
    • Frequency variation measurement;
    • Power outages;
  • Load profile recording:
    • Number of channels: 8 (+A, -A, R1, R2, R3, R4, +W, -W);
    • Load profile capacity: up to 341 days with integration period of 60 minutes;
    • Programmable integration period: from 30 sec to 60 min.

    Data Storage

    PTD-2G device has 1 MB of non-volatile memory, which allows to store metering data without influence of power outages. Capacity of stored data:
  • Total energy
  • [T1...T8, TS];
  • Monthly energy
  • [T1...T8, TS], at least 54 months;
  • Daily energy
  • [T1...T8, TS], at least 100 days;
  • Cumulative maximum demand
  • [T1...T8];
  • Monthly maximum demand
  • [T1...T8], at least 54 months, with date and time;

  • Daily maximum demand
  • [T1...T8], at least 100 days, with date and time;

  • Load profiles
  • up to 8 channels;
  • Instantaneous values
  • up to 16 programmable channels for any of
    26 instantaneous value;

    Features
  • Powered by measuring circuits
  • Current measuring range (1mA ... 200A)
  • Electronic test output
  • Current Loop, RS 232 and USB interfaces for connection to PC
  • Current loop interface according to IEC62056-31 for connection to AMR system
  • Non-volatile memory for data storage


  • Technical specification:

     Ratings  
     Rated voltage, V:  50 ... 276V
     Measuring period, s  1
     Power consumption, VA:  2/phase
     Frequency range, Hz:  45 ... 65
     Operating temperatures  -10°C … +50°C
     Storage and transportation temperatures  -35°C … +50°C
     Relative humidity:  Up to 80% (t=25°С)
     Current clamps  
     Current range 0,1 A...200 A (Clamps MG8)  
     Phase voltage, V  50…254
     Line-to-line voltage, V  100…440
     Current range 0,001 A...0,3 A (direct connection)  
     Phase voltage, V  50…254
     Line-to-line voltage, V  100…440
     External backup power supply  
     Input/output voltage, V  »230/(=12..14)
     Current, mA  500
     Case & Dimensions  
     Case:  UV stabilized polycarbonate
     Insulation:  Protective class 2
     Measuring unit dimensions:  157 x 189 x 67 mm
     Measuring unit weight:  2 kg
     Protection level:  IP 52