|LT |EN |RU |SP|
  HOMEMAILSITEMAPPRINT
GEM-T

GEM-T

The electronic single-phase meter GEM-T has been developed for the measurement of active energy in 50 Hz and 60 Hz networks. Meter complies with Standards IEC 62052-11 and IEC 62053-21 requirements for accuracy class 1.0.
GEM-T meter has drum register for the display of active energy in one tariff. Meters register active energy irrespectively of energy direction, i.e. the registration takes place on the same register at +A. The pulse outputs for LED and electrical test output are active in both energy directions, too.

Features:


Measuring

Meter operates in singe-phase electricity networks and independently from current flow direction measure:
  • Active energy with accuracy class 1.0 or 2.0 (IEC 62053-21)
  • Outputs

  • Electric pulse output (S0)
  • LED test output for active energy
  • Two status indicators (LEDS) - , ~



  • Indicator status Meaning
    ~
    Off Off No network voltage
    For 5 seconds on, when meter starts For 5 seconds on, when meter starts Normal start
    Off On Normal operation
    Off Blinking No load
    Blinking On Reverse current
    On Off Meter malfunction

    Display

    GEM-T meter is equipped with traditional electromechanical drum-register. Register can be either 5+1 or 6+1 digits, which offers sharp readability when compared to electronic displays. The register offers the additional advantage of allowing the meter to be read when power is absent with no need to use power backup.

    Technical Specification:

    Ratings

     
    System Single-Phase 2-wire
    Accuracy class Class 1.0 or Class 2.0
    Reference voltage, Un 100V; 120V; 127V; 220V; 230V;
    special on request
    Reference (maximum) current, Ib (Imax) 5(60) A; 5(85) A; 10(60) A; 10(100) A
    Current threshold 0,4% Ib
    Reference Frequency, Hz 50 or 60
    Meter constant, imp/kWh 2000 or 4000
    Power consumption:
    In voltage circuit
    In current circuit

    < 0,5W; < 5 VA
    < 0,05 VA
    Temperature ranges:
    Meter operating
    Meter storage

    -40°C to +60°C
    -50°C to +70°C

    Case & Dimensions

     
    Case UV stabilized polycarbonate
    Insulation Protective class II
    Degree of protection IP51
    Dimensions, mm 230 x 132 x 59
    Weight, kg 0,8

    Downloads: