GAMA 300
GAMA 300
New meter GAMA 300 is developed for a very rapidly changing electricity market, adapted to deregulation and customers' growing demands. Electronic electricity meter GAMA 300 operates in three-phase electricity networks and is approved in accordance with the standards IEC 62052-11, IEC 62053-21, IEC 62053-23, EN 50470-1 and EN 50470-3. The electricity meter satisfies the requirements of Directive 2004/22/EC of the European Parliament and of the Council of 31 March 2004 on measuring instruments.
Meter has optical and electrical communication interfaces and additionally can be equipped with internal communication modules upon request, allowing easy connection of meters to AMR system directly. GAMA 300 meter can have changeable (without uninstalling meter from site) Li-ion battery and internal relay for remote user disconnection.
Meter has optical and electrical communication interfaces and additionally can be equipped with internal communication modules upon request, allowing easy connection of meters to AMR system directly. GAMA 300 meter can have changeable (without uninstalling meter from site) Li-ion battery and internal relay for remote user disconnection.
Features:

Measuring
Meter operates in three-phase electricity networks and measures:
Tariff module
Meter GAMA 300 can be single-tariff or multi-tariff. Multi-tariff modification of the meter GAMA 300 has internal real-time clock with Li-ion or Super-cap backup and complex tariff structure (Time-Of-Use):
|
|
Up to 4 tariffs; |
|
|
Up to 12-tariff seasons; |
|
|
Up to 10-week profiles; |
|
|
Up to 16-day profiles; |
|
|
Up to 365 fixed and 16 movable days; |
|
|
Up to 4 tariffs; |
|
|
Programmable. |
Billing
At the end of the billing period, the billing period reset signal triggers the storage of the current values to the non-volatile memory. The billing period reset may be initiated:
|
|
by pressing push-button; |
|
|
on decade days; on ½ month; on predefined day |
Data storage
GAMA 300 meter has non-volatile memory, which allows to store metering data without influence of power outages. Capacity of stored data:
|
|
from installation date; |
|
|
of last 16 months; |
|
|
up to 480 days; |
|
|
of last 12 months; |
|
|
up to 32 records of each event type; |
|
|
up to 4 channels. |
Load Profiles [Optional]
In order to help utilities and customers to meet deregulated market needs, meter GAMA 300 can have load profiles:
|
|
up to 252 days with integration period 60 minutes; |
|
|
5, 10, 15, 20, 30 or 60 min. |
Communications
Meter has optical communication interface in accordance with IEC62056-21 or DLMS. Optical communication interface allows the user to read data and program meter in the field or in the workshop. GAMA 300 meter can have up to two electrical communication interfaces, allowing connection of meters to AMR system through external GSM/GPRS, RF, PSTN and LAN controllers:
- 20 mA current loop (protocols: IEC 62056-21 or IEC 62056-31 or DLMS)
- 20 mA current loop (protocol IEC 62056-31 or DLMS)
- RS485 (protocol IEC 62056-31 or DLMS)
- RS232 (protocol IEC 62056-31 or DLMS)
- M-bus (protocol M-bus) for retrieving data from Water, Gas, Heat meters
Outputs/Inputs
- When specified energy tariff is valid;
- For two programmed periods during the 24-hour interval (periods are set in 15 minutes step).
[Optional] Internal disconnection relay
Internal disconnection relay is used to disconnect/reconnect electricity to the user. User disconnection may be done by the following means:
Automatically when contractual power limit is exceeded;
By external signal through communication interfaces.
The user himself does reconnection by pressing a scroll-push button on the meter. This ensures maximum safety to the user.
The user himself does reconnection by pressing a scroll-push button on the meter. This ensures maximum safety to the user.
Security features
Hardware protection allows only authorized persons to access meter:
Meter with internal clock has Events logbook, registering the following events:
|
|
total #, last 32 events with date & time |
|
|
last 10 events with date & time |
|
|
last 10 events with date & time |
|
|
total #, last 10 events with date & time |
|
|
error code, last event with date & time |
|
|
total #, duration, last event with date & time |
|
|
duration, last event with date & time |
|
|
total #, duration, last event with date & time |
|
|
total #, duration, last event with date & time |
Display
GAMA 300 meter is equipped with LCD (Liquid crystal display). LCD contains 8 digits with programmable decimal point: 8-5 for whole numbers and 0-3 digits for decimal numbers. LCD displays majority of data accumulated in meter and parameterization constants. Features:
Technical Specification:
|
Ratings |
|
| System | Three-phase 4-wire or 3-wire |
| Accuracy class: For active energy For active energy (CT/VT connection) For reactive energy |
Class 1.0 or 2.0 (IEC 62053-21), Class A or B (EN 50470-3) Class 0.5s (IEC 62053-22), Class C (EN 50470-3) Class 2.0 (IEC 62503-23) |
| Reference voltage, Un: 4 wire networks Multi-range (CT/VT connection) 3 wire networks |
3x57,7/100; 3x63,5/110; 3x69,2/120; 3x120/208; 3x127/220; 3x220/380; 3x230/400 3x57,7/100...230/400; 3x100...230 3x100; 3x110; 3x220; 3x230; 3x120 |
| Reference (max.) current, Ib (Imax): Direct connection, A CT or CT/VT connection, A |
5(60); 5(80); 5(100); 10(60); 10(80); 10(100); 1(1,25); 1(2); 1(6); 5(6,25); 5(10) |
| Current threshold | 0,4% Ib (0,2% In if CT or CT/VT connection) |
| Reference Frequency, Hz | 50 or 60 |
| Meter constant, imp/kWh |
1...19999 (direct connection), 1...60000 (CT or CT/VT connection) |
| Power consumption: In voltage circuit In current circuit |
< 0,5 W; < 1 VA < 0,05 VA (< 0,5 VA if CT or CT/VT connection) |
| Temperature ranges: Meter operating Meter storage |
-25°C to +55°C (normal) -40°C to +70°C (extended) -50°C to +70°C |
| Internal real-time clock | |
| Accuracy | < 0,5 s/24 h, T = 23 °C (IEC 62054-21) |
| Backup power supply | Li-ion battery or Super Cap (rechargeable) |
| Li-ion battery | Changeable on operating meter or internal |
| Operation duration using only backup: Li-ion battery Super Cap |
> 10 years > 7 days |
| [Optional] Internal bi-stable disconnection relay |
|
| Maximum commutation voltage, V | 440 |
| Maximum commutation current, A | 120 |
| Maximum commutation power, VA | 28000 |
| Number of life switching operations | 105 |
|
Case & Dimensions |
|
| Case | UV stabilized polycarbonate |
| Insulation | Protective class II |
| Degree of protection | IP53 |
| Dimensions, mm | 260x175x80 |
| Weight, kg | < 1,3 |
Downloads:
Product brochure
More information about the meter available to download can be found here
Other products >>