Equipo portátil de verificación de medidores
PTD-3G
PTD - 3G (Portable Testing Device) is a portable electronic device for on site meter testing, measurement of instantaneous values and profile recording. The device also provides some features of network quality monitoring. It is suitable for testing of single-phase and three-phase electricity meters on site, for energy quality and network parameters monitoring.
Wide range of functions, user - friendly interface, and sizeable graphical LCD applicable for diagram indication make the working with this device easy, accurate and attractive.
Application
On site testing of inductive and electronic single-phase and three-phase electricity meters
Power quality monitoring (according to the standard IEC50160)
Measurement of instantaneous values
Profile recording
Functions
Active, reactive and apparent energy measurement with error calculation (percentage):
Active, reactive and apparent energy measurement with start / stop function
Meter accuracy, constant, wiring, no load/start condition testing
Active, reactive, apparent power measurement (per phase and aggregate):
Voltage measurement:
Current measurement:
Power factor measurement (per phase and aggregate):
Frequency measurement:
Harmonics analysis:
Vector diagram displaying
Measurement of angles:
Power quality measurement:
Wide range of functions, user - friendly interface, and sizeable graphical LCD applicable for diagram indication make the working with this device easy, accurate and attractive.

Application
Functions
- Measurement error of active energy (cosφ=1):
- ±0,5 % with clamps A (0,5...100 A);
- ±0,5 % with clamps B (1...1000 A);
- ±0,5 % with clamps C (10...1500 A).
- Measurement error:
- ±0,5 % with clamps A (0,5...100 A)
- ±0,5 % with clamps B (1...1000 A)
- ±0,5 % with clamps C (10...1500 A)
- Frequency range: 45...65 Hz;
- Error: ±0,2 % in range 50 ...265 V
- Frequency range: 45...65 Hz;
- Current range: depends on current clamps;
- Measurement error:
- ±0,5 % with clamps A (0,5...100 A)
- ±0,2 % with clamps B (1...1000 A)
- ±0,5 % with clamps C (10...1500 A)
- Measurement range -1...+1;
- Resolution: 0,01
- Range 45...65 Hz;
- Resolution 0,01 Hz
- Harmonic components from 2 to 30 in - percent of the fundamental wave;
- Numeric values of each harmonic component;
- Chart in a logarithmic scale
- Voltage phase shift angles (per phase and aggregate), resolution: 0,1°
- Angles between voltage phases, resolution: 1°
- Voltage variation measurement (according EN50160)
- Frequency variation measurement (according EN50160)
- Total harmonics distortion
- Power outages
Data Storage
Features
Technical Specification:
|
Power supply |
|
| Powered by voltage measuring circuits | 45 V... 276 V, consumption: < 2 W per phase |
| Powered by auxiliary circuit | 45 V... 276 V, consumption: < 6 W |
| Profiles | |
| Number of channels for profile recording: | 6 with 25 different parameters available |
| One of 5 registration algorithms for each channel: |
Minimum value per measurement period Maximum value per measurement period Average value per measurement period Snapshot at the end of measurement period Standard deviation per measurement period |
| Range of measurement period: | 10s...60 min |
| Current clamps | |
| Current range 0,5 A...100 A (Clamps A) | |
| Electrical safety: Insulation: Pollution: Safety class: Operating voltage: Bare conductor Isolated conductor |
Dual Level 2 Class III 30V 600V |
| Overload: | 170 A |
| Protection level: | IP40 |
| Weight: | ~ 0,16 kg |
| Max. Clamping capacity: Cable, mm: Bus bar, mm: |
Ø12 17 x 15 |
| Current range 1 A...1000 A (Clamps B) | |
| Electrical safety: Insulation: Pollution: Safety class: Operating voltage: |
Dual Level 2 Class III 600V |
| Overload: | 1200 A |
| Protection level: | IP40 |
| Weight: | ~ 0,55 kg |
| Max. Clamping capacity: Cable, mm: Bus bar, mm: |
Ø52 50 x 5 |
| Current range 10 A...1500 A (Clamps C) | |
| Electrical safety: Insulation: Pollution: Safety class: Operating voltage: Bare conductor Isolated conductor |
Dual Level 2 Class III 600V, 1000V |
| Overload: | 1800 A |
| Protection level: | IP20 |
| Scanning head | |
| Usable with: | Induction and electronic meters |
| Supply voltage: | 6...12 V |
| Dimensions: | 270mm x 95mm x 80mm |
| Electronic block | |
| Max. Clamping capacity: Cable, mm: Bus bar, mm: |
Ø80 100x 55 or 120 x 45 |
| Housing: | Hard plastic |
| Dimension: | 157 x 189 x 67 mm |
| Weight: | 0.8 kg |
| Operation temperature: | -20 °C ... + 50 °C |
| Protection level: | IP 40 |